Delta’s feature-rich DIN rail power supplies offers start-up at -40°C, Advanced Power Boost and smart monitoring functions on selected CliQ models. To fulfill the demands in maritime applications, CliQ M series complies with ABS and DNV-GL safety standards. Several CliQ models are also certified to ATEX and Class I, Div 2 for use in hazardous locations.
₹ 1000 / Piece Get Latest Price
| Material | Aluminum |
| Mounting Type | DIN Rail |
| Brand | Delta |
| Model Name/Number | DRP024V240W1BA |
| Country of Origin | Made in India |
| Output Current | 10A |
| Output Voltage | 24V |
| Output Voltage Adjustment Range | 24-28Vdc |
| Output Power | 240W |
| Nominal Input Voltage | 100-240Vac |
| Input Voltage Range | 85-264Vac |
| Nominal Input Frequency | 50-60Hz |
| Input Frequency Range | 47-63Hz |
| Inrush Current | < 35A @ 115Vac & 230Vac |
| Leakage Current | < 1mA @ 240Vac |
| Case Chassis / Cover | Aluminium |
| Indicator | Green LED (DC OK) |
| Cooling System | Convection |
| Mounting Rail | Standard TS35 DIN Rail in accordance with EN 60715 |
| Unit Weight | 1.10 kg (2.43 lb) |
| Dimensions | 121 x 85 x 124.1 mm 4.76" x 3.35" x 4.89" |
| Operating Temperature | -25 DegreeC to +80 DegreeC (Cold Start at -40 DegreeC) |
| Storage Temperature | -40 DegreeC to +85 DegreeC |
| Power De-rating | Vertical: > 50 DegreeC de-rate power by 2.5% / DegreeC Horizontal: > 40 DegreeC de-rate power by 2.5% / DegreeC |
| Operating Humidity | 5 to 95% RH (Non-Condensing) |
| Over Voltage Category | III According to IEC/EN 62477-1 / EN 60204-1 (clearance and creepage distances) and IEC 62103 (safet |
| Overvoltage | < 32V, +-10%, SELV Output, Hiccup Mode, Non-Latching (Auto-Recovery) |
| Overload / Overcurrent | > 150% of rated load current, Hiccup Mode, Non-Latching (Auto-Recovery) |
| Over Temperature | < 80 DegreeC Surrounding Air Temperature @ 100% load, Non-Latching (Auto-Recovery) |
| Short Circuit | Hiccup Mode, Non-Latching (Auto-Recovery when the fault is removed) |
| Degree of Protection | IP20 |
| Protection Against Shock | Class I with Primary Earth connection |
| MTBF | > 500,000 hrs. as per Telcordia SR-332 (I/P: 115Vac, O/P: 100% load, Ta: 25 DegreeC) |
| Expected Cap Life Time | 10 years (115Vac & 230Vac, 50% load @ 40 DegreeC) |
| Electrical Safety | SIQ Bauart: EN 62368-1 UL/cUL recognized: UL 60950-1 and CSA C22.2 No. 60950-1 (File No. E191395), U |
Minimum order quantity: 1 Piece
₹ 1000 / Piece Get Latest Price
| Material | Aluminum |
| Mounting Type | DIN Rail |
| Brand | Delta |
| Model Name/Number | DRP048V240W1BA |
| Country of Origin | Made in India |
| Output Current | 5A |
| Output Voltage | 48V |
| Output Voltage Adjustment Range | 48-56Vdc |
| Output Power | 240W |
| Line Regulation | < 0.5% (@ 85-264Vac input, 100% load) |
| Nominal Input Voltage | 100-240Vac |
| Input Voltage Range | 85-264Vac |
| Nominal Input Frequency | 50-60Hz |
| Input Frequency Range | 47-63Hz |
| DC Input Voltage Range | 120-375Vdc |
| Operating Temperature | -25 DegreeC to +80 DegreeC (Cold Start at -40 DegreeC) |
| Storage Temperature | -40 DegreeC to +85 DegreeC |
| Power De-rating | Vertical: > 50 DegreeC de-rate power by 2.5% / DegreeC Horizontal: > 40 DegreeC de-rate power by 2.5% / DegreeC |
| Operating Humidity | 5 to 95% RH (Non-Condensing) |
| Over Voltage Category | III According to IEC/EN 62477-1 / EN 60204-1 (clearance and creepage distances) and IEC 62103 (safet |
| Overvoltage | < 57V, SELV Output, Hiccup Mode, Non-Latching (Auto-Recovery) |
| Overload / Overcurrent | > 150% of rated load current, Hiccup Mode, Non-Latching (Auto-Recovery) |
| Over Temperature | < 80 DegreeC Surrounding Air Temperature @ 100% load, Non-Latching (Auto-Recovery) |
| Short Circuit | Hiccup Mode, Non-Latching (Auto-Recovery when the fault is removed) |
| Degree of Protection | IP20 |
| Protection Against Shock | Class I with Primary Earth connection |
| MTBF | > 500,000 hrs. as per Telcordia SR-332 (I/P: 115Vac & 230Vac, O/P: 100% load, Ta: 25 DegreeC) |
| Expected Cap Life Time | 10 years (115Vac & 230Vac, 50% load @ 40 DegreeC) |
| Electrical Safety | SIQ Bauart: EN 62368-1 UL/cUL recognized: UL 60950-1 and CSA C22.2 No. 60950-1 (File No. E191395), U |
| Galvanic Isolation | Input to Output: 4.0 KVac Input to Ground: 1.5 KVac Output to Ground: 1.5 KVac |
| Electrical Equipments of Machines | EN/BS EN 60204-1 (over voltage category III) |
| Safety Entry Low Voltage | SELV (IEC 60950-1) |
| UKCA | In conformance with Electrical Equipment (Safety) Regulations 2016 No. 1011 and The Electromagnetic |
| Emission | (CE & RE) Generic Standards: CISPR 32, EN/BS EN 55032, KN 32, CNS 13438, CISPR 11, EN/BS EN 55011, F |
| Immunity | Generic Standards: EN/BS EN 55024, KN 35, EN/BS EN 61000-6-1, EN/BS EN 61000-6-2 |
Minimum order quantity: 1 Piece
₹ 1000 / Piece Get Latest Price
| Output Voltage | 24V DC |
| Dimensions (L x W x H) | 121 x 70 x 117.3 mm 4.76" x 2.76" x 4.62" |
| Output Current | 10A |
| Short Circuit | Hiccup Mode, Non-Latching (Auto-Recovery when the fault is removed) |
| Country of Origin | Made in India |
| Model Name / Number | DRP024V240W3BA |
| Mounting Type | DIN Rail |
| Brand | Delta |
| Output Voltage Adjustment Range | 24-28Vdc |
| Output Power | 240W |
| Nominal Input Voltage | 3 x 400-500Vac |
| Input Voltage Range | 3 x 320-600Vac |
| Nominal Input Frequency | 50-60Hz |
| Input Frequency Range | 47-63Hz |
| Case Chassis / Cover | Aluminium |
| Indicator | Green LED (DC OK) |
| Cooling System | Convection |
| Input Terminal | 4 Pins (Rated 600V/35A) |
| Output Terminal | 4 Pins (Rated 300V/28A) |
| Noise Sound Pressure Level (SPL) | < 40dBA |
| Mounting Rail | Standard TS35 DIN Rail in accordance with EN 60715 |
| Unit Weight | 0.89 kg (1.96 lb) |
| Operating Temperature | -25 DegreeC to +80 DegreeC |
| Storage Temperature | -40 DegreeC to +85 DegreeC |
| Operating Humidity | 0 to 95% RH (Non-Condensing) |
| Overvoltage | 32V +-10%, SELV Output, Hiccup Mode, Non-Latching (Auto-Recovery) |
| Overload / Overcurrent | > 150% of rated load current, Hiccup Mode, Non-Latching (Auto-Recovery) |
| Over Temperature | < 80 DegreeC Surrounding Air Temperature @ 100% load, Non-Latching (Auto-Recovery) |
| Degree of Protection | IP20 |
| Protection Against Shock | Class I with Primary Earth connection |
| MTBF | > 500,000 hrs. as per Telcordia SR-332 (I/P: 3 x 400Vac, O/P: 100% load, Ta: 25 DegreeC) |
| Expected Cap Life Time | 10 years (3 x 400Vac & 3 x 500Vac, 50% load @ 40 DegreeC) |
| Electrical Safety | SIQ Bauart: EN 62368-1 UL/cUL recognized: UL 60950-1 and CSA C22.2 No. 60950-1 (File No. E191395), U |
| Safety Entry Low Voltage | SELV (IEC 60950-1) |
| UKCA | In conformance with Electrical Equipment (Safety) Regulations 2016 No. 1011 and The Electromagnetic |
Minimum order quantity: 1 Piece
Amit Bheda (Director)
Analog Corporation
R.S.No. 171, Plot No 27 - 32, Classic Industrial Area, Dhebar Road - South, Rajkot - 360001, Gujarat, India